Siemens F002 Fault -

| Drive Supply Voltage | DC Link Trip Level (approx.) | |----------------------|------------------------------| | 230V (1-phase) | 410 – 420 V DC | | 400V (3-phase) | 820 – 850 V DC | | 690V (3-phase) | 1100 – 1150 V DC |

Always verify the braking chopper and resistor health before replacing the drive – a new drive will trip F002 just as fast if the external braking circuit is faulty. For specific parameter numbers, always refer to the drive’s current parameter manual, as Siemens occasionally updates parameter lists between firmware versions. siemens f002 fault

1. Overview Fault Code: F002 Associated Systems: Siemens SINAMICS (G120, S120, G130, G150) and legacy MASTERDRIVES (6SE70). Fault Class: Overvoltage / DC link overvoltage. Immediate Reaction: Drive trips (OFF2), motor coasts to a stop. | Drive Supply Voltage | DC Link Trip Level (approx